Cable cross-section calculator online
Calculate cable cross-section online. Enter the required dimensions and parameters to estimate quantities and key values.
01 / Calculation method
Cable cross-section calculation
The calculator suggests a copper or aluminum cable cross-section from load current or power, line length, voltage drop, and installation method. It supports preliminary cable selection for socket circuits, lighting, motors, pumps, workshops, and small three-phase loads.
The result does not replace an electrical design. Before installation, check the selected cross-section against applicable standards, protective device, insulation type, temperature, number of loaded cores, installation conditions, and cable manufacturer’s requirements.
Design current
For a known single-phase load power, current is:
For a three-phase supply:
where is current in amperes, is active power in watts, is supply voltage, and is power factor. It is close to 1 for heaters and commonly 0.8–0.95 for motors and pumps.
Allowable current check
The calculator compares design current with tabulated allowable currents for the selected conductor material and installation method. A cable in conduit or grouped with other cables cools less effectively, so allowable current is reduced. Grouped installation uses a correction factor.
Voltage-drop check
Even when a cable passes the thermal check, a long line may have excessive voltage drop. The calculation uses:
where is voltage drop, for a single-phase line and for a three-phase line, is line resistance, is inductive reactance, and is load current.
Active resistance is adjusted for line length and temperature:
where is conductor resistance per meter, is one-way line length, is a material correction, is the temperature coefficient, and is cable operating temperature.
Voltage drop as a percentage is:
Selecting the final cross-section
The calculator finds a minimum cross-section for allowable current and another for voltage drop. The recommendation uses the more restrictive condition:
This avoids two common problems: the cable must not overheat under load, and a long run must not cause excessive voltage drop.
Factors affecting accuracy
Actual cable selection depends on cable make, insulation type, ambient temperature, installation method, number of simultaneously loaded conductors, load duration, motor starting current, protective device characteristics, and IEC 60364 or local electrical rules. Treat this online power and current calculation as a preliminary guide, not a final design decision.
PUE tables: allowable continuous current
The following reference tables from the Electrical Installation Rules (PUE) are used by the calculator algorithm. They can also support manual current-based section selection for single- and three-phase loads.
Copper conductors (PUE Table 1.3.4)
Allowable continuous current for copper wires with rubber or PVC insulation:
| Conductor area, mm² | In air (open), A | In ground (trench), A | In one conduit (2-core), A | In one conduit (3-core), A |
|---|---|---|---|---|
| 0.5 | 11 | 17 | — | — |
| 0.75 | 15 | 23 | — | — |
| 1.0 | 17 | 26 | 15 | 14 |
| 1.5 | 23 | 33 | 18 | 15 |
| 2.5 | 30 | 44 | 25 | 21 |
| 4.0 | 41 | 57 | 32 | 27 |
| 6.0 | 50 | 68 | 40 | 34 |
| 10.0 | 80 | 99 | 55 | 50 |
| 16.0 | 100 | 125 | 80 | 70 |
| 25.0 | 140 | 162 | 100 | 85 |
| 35.0 | 170 | 192 | 125 | 100 |
| 50.0 | 215 | 238 | 160 | 135 |
| 70.0 | 270 | 294 | 195 | 175 |
| 95.0 | 330 | 353 | 245 | 215 |
| 120.0 | 385 | 395 | 295 | 250 |
Aluminum conductors (PUE Table 1.3.5)
Allowable continuous current for aluminum wires and cables with rubber or plastic insulation:
| Conductor area, mm² | In air (open), A | In ground (trench), A | In one conduit (2-core), A | In one conduit (3-core), A |
|---|---|---|---|---|
| 2.5 | 24 | 33 | 19 | 16 |
| 4.0 | 32 | 44 | 25 | 21 |
| 6.0 | 39 | 52 | 31 | 26 |
| 10.0 | 60 | 75 | 42 | 38 |
| 16.0 | 75 | 96 | 60 | 55 |
| 25.0 | 105 | 124 | 75 | 65 |
| 35.0 | 130 | 147 | 95 | 75 |
| 50.0 | 165 | 182 | 125 | 105 |
| 70.0 | 210 | 224 | 160 | 135 |
| 95.0 | 255 | 269 | 190 | 165 |
| 120.0 | 295 | 301 | 230 | 190 |
02 / Frequently asked questions
Should I calculate by current or by power?
If the equipment rating gives current in amperes, use current mode. If you only know the total load power, choose power mode; the calculator converts it to current using voltage, phase count, and power factor.
Why does cable length affect cross-section?
The longer the cable, the higher its resistance and the greater the voltage drop at the load. A long run may therefore need a larger cross-section even if a smaller cable meets the current-carrying table value.
Why does aluminum need a larger cross-section?
Aluminum has higher electrical resistance than copper. At the same current, an aluminum cable has greater voltage drop and a lower tabulated current capacity, so the calculator often recommends a larger nominal size.
Why does installation method change the result?
An openly installed cable cools better. In conduit, trunking, or a group of cables, heat dissipates less effectively and allowable current is reduced. The calculator accounts for this using table values and correction factors.
What voltage-drop percentage should I use?
For household circuits, 3–5% is a common guide. Choose a lower drop for lighting and sensitive equipment. A higher drop may be acceptable for a short power circuit if the design and applicable rules allow it.
Can I use the result as a final wiring design?
No. The online cable cross-section calculator gives a preliminary selection. A real installation also needs checks for the protective device, short-circuit current, earthing arrangement, cable type, installation conditions, and current electrical rules.