Circuit breaker sizing by power calculator online

Calculate circuit breaker sizing by power online. Enter the required dimensions and parameters to estimate quantities and key values.

DOC_REF // CALC-CIRCUIT-BREAKER-SIZING-BY-POWER

Network and load

Section Reserve

Enter the value using the units shown. Check the measurements before calculating.
The installation method affects current capacity. Cables cool less effectively in conduit and grouped runs.

Selected network-
Selected Power-
Line-
Group Consumers-
demand Factor-
effective Power-
Power Factor-
Selected Reserve-
Selected Temperature-
install Factor-

working Current0 A
design Current0 A
breaker Nominal0 A
lower Breaker0 A
real Margin0 %
copper Section-
aluminium Section-

Results are estimates. Check the dimensions and verify the design against local requirements before construction., mm²

01 / Calculation method

Circuit breaker sizing by power

The calculator suggests a preliminary circuit breaker rating based on the total load, 230/400 V supply type, power factor, current allowance, and demand factor for a group of loads. It also shows approximate copper and aluminum cable cross-sections that should carry the selected breaker rating for the specified temperature and installation method.

Use this estimate for an initial check of a socket circuit, individual appliance, pump, workshop, or small three-phase line. It does not replace an electrical design: the breaker must protect the cable, not merely match the appliance power.

Design power

For a group of loads, the demand factor is applied:

Peff=P⋅kP_{eff} = P \cdot k

where PeffP_{eff} is the design power, PP is the installed power, and kk is the demand factor. For a single load, k=1k = 1.

Converting power to current

For a single-phase supply:

Iwork=Peff⋅1000U⋅cosφI_{work} = \frac{P_{eff} \cdot 1000}{U \cdot cos\varphi}

For a three-phase supply:

Iwork=Peff⋅10003⋅U⋅cosφI_{work} = \frac{P_{eff} \cdot 1000}{\sqrt{3} \cdot U \cdot cos\varphi}

Here, IworkI_{work} is the load operating current, UU is the supply voltage, and cosφcos\varphi is the power factor. At the same active power, a lower power factor results in a higher current.

Current allowance and breaker selection

The operating current is increased by the selected allowance:

Icalc=Iwork⋅(1+r100)I_{calc} = I_{work} \cdot (1 + \frac{r}{100})

where rr is the current allowance in percent. The calculator then selects the smallest standard breaker rating that is not below IcalcI_{calc} from the series 6, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, and 100 A.

The selected breaker’s actual current margin is:

M=(InIcalc−1)⋅100M = (\frac{I_n}{I_{calc}} - 1) \cdot 100

Cable cross-section estimate

The cable estimate uses the selected breaker rating and correction factors for the installation conditions:

Itab=InkT⋅kMI_{tab} = \frac{I_n}{k_T \cdot k_M}

where ItabI_{tab} is the current used to select a cross-section from a table, kTk_T is the temperature factor, and kMk_M is the installation-method factor. Poorer cable cooling lowers the correction factor and requires a larger cross-section.

Important limits

The calculator does not check voltage drop, short-circuit current, selectivity, B/C/D trip curves, motor starting currents, or requirements for a specific cable run. For final selection, refer to IEC/HD 60364, EN/IEC 60898-1, EN/IEC 60947-2, and local electrical installation rules.

02 / Frequently asked questions

What is the difference between operating current and design current with an allowance?

Operating current is calculated directly from power, voltage, and cosφcos\varphi. Design current includes the selected allowance. The breaker is sized from this higher value so it is not too close to the continuous load.

Why is current lower in a three-phase system for the same power?

In a three-phase system, power is distributed across three phases and the formula includes a factor of 3\sqrt{3}. At the same total power, line current is therefore usually lower than in a 230 V single-phase system.

Can I choose the next lower breaker rating?

The next lower rating is shown for comparison only. Usually, you select the smallest standard breaker rating that is not below the design current. A lower rating may trip during sustained operation.

Why does the calculator show a cable cross-section?

A circuit breaker must protect the conductor from overheating. After selecting a rating, check that the cable can carry that current for the given temperature and installation method.

Is this calculation enough for installation?

No. A real panel design also needs checks for voltage drop, short-circuit current, breaker B/C/D trip curve, selectivity, and local electrical installation requirements.