Room lighting calculator online

Calculate room illuminance or select the number of fixtures from floor area, room type, required lighting level, luminous flux, and a maintenance factor.

DOC_REF // CALC-ROOM-LIGHTING

Input data

Calculation diagram

Result Total Flux0 Unit Lm
Result Illumination0 Unit Lx
Result Fixtures Count0 pcs
Result Fixture Flux0 Unit Lm

Results are estimates. Check the dimensions and verify the design against local requirements before construction.

01 / Calculation method

Room lighting calculation

This calculator supports preliminary lighting selection for residential, office, commercial, and industrial rooms. From the room area, target illuminance, and reserve factor, it estimates the total luminous flux required and the number of fixtures or luminous flux required per fixture.

Calculation steps

The calculation links illuminance in lux with luminous flux in lumens.

1. Room area AA

If room length LL and width WW are entered in meters, area is:

A=L⋅WA = L \cdot W

If area is entered directly, it is used as provided: A=SinputA = S_{input}.

2. Required total luminous flux Φtotal\Phi_{total}

Total luminous flux in lumens is calculated from target illuminance EmE_m, room area AA, and reserve factor kk:

Φtotal=Em⋅A⋅k\Phi_{total} = E_m \cdot A \cdot k

where:

  • EmE_m is target average illuminance on the working plane, in lx;
  • AA is room area in m²;
  • kk is the reserve factor.

3. Select a parameter for the chosen calculation mode

The calculator finds one of these values:

  • By number of fixtures: from a specified fixture count NN, it finds luminous flux per fixture Φ1\Phi_1 in lm:

    Φ1=ΦtotalN\Phi_1 = \frac{\Phi_{total}}{N}
  • By luminous flux per fixture: from one fixture’s luminous flux Φ1\Phi_1 in lm, it finds the required number of fixtures NN:

    N=⌈ΦtotalΦ1⌉N = \lceil \frac{\Phi_{total}}{\Phi_1} \rceil

    Here, ⌈x⌉\lceil x \rceil means rounding up to the next whole number.

4. Calculated illuminance with reserve factor

Calculated illuminance is the target value adjusted by the reserve factor:

Ecalc=Em⋅kE_{calc} = E_m \cdot k

Reserve factor kk

The reserve factor accounts for lamp aging and reduced output, as well as dust on fixtures and reflective room surfaces during operation.

  • k=1.0k = 1.0: no allowance, ideal conditions;
  • k=1.2k = 1.2: moderate allowance for clean homes and offices with regular maintenance;
  • k=1.5k = 1.5: average allowance for public and educational spaces;
  • k=2.0k = 2.0: higher allowance for outdoor lighting or dusty areas.

02 / Frequently asked questions

Why is luminous flux measured in lumens while the target is in lux?

Lux is illuminance: one lux equals one lumen per square meter (1 lx=1 lm/m21\text{ lx} = 1\text{ lm/m}^2). Given the room area, the target illuminance can be converted into total luminous flux with Φtotal=Em⋅A⋅k\Phi_{total} = E_m \cdot A \cdot k.

What does reserve factor k mean, and why is it greater than 1?

The reserve factor accounts for lamps losing output over time and for dust accumulating on fixtures and room surfaces. For example, k=1.2k = 1.2 adds 20% more luminous flux to compensate for these operating losses.

Why is the number of fixtures rounded up?

If the calculation requires 5.2 fixtures, six must be installed. Rounding up helps ensure that room illuminance is not below the target value.

Can this calculation give an exact illuminance at a workstation?

This calculator gives a preliminary estimate based on total luminous flux across the whole area. Illuminance at a specific point depends on light distribution, fixture mounting height, wall and ceiling reflectance, and lamp beam angle. Important projects need a professional lighting calculation in specialized software such as DIALux.

Indoor workplaces and rooms commonly follow EN 12464-1, while outdoor areas use EN 12464-2. The calculator provides standard recommendations for common room types, but you can enter another target manually.