Wire resistance calculator online

Calculate conductor resistance and voltage drop from material, length, and cross-section. Include conductor temperature, load current, and supply voltage to assess a line.

DOC_REF // CALC-WIRE-RESISTANCE

Cable material

Dimensions

Options

Hint Option Temperature, °C, °
Hint Option VDrop
Graph Title
050100Length L, m0510Graph Axis R

Material-
Cross-section, mm²- mm²
Length- m

Result ROne- Unit Ohm
Result RLoop- Unit Ohm
Result RPer m- Unit Ohm m
Result GOne- With

01 / Calculation method

Electrical resistance depends on the conductor’s material resistivity, length, cross-sectional area, and operating temperature. This calculator evaluates line parameters using standard electrical engineering equations.

Calculation steps

1. Conductor geometry

Depending on the selected input mode, the calculator determines the cross-sectional area SS in mm² or the conductor diameter dd in mm. If the area is specified, the diameter is:

d=4⋅Sπd = \sqrt{\frac{4 \cdot S}{\pi}}

If the diameter is specified, the equivalent cross-sectional area is:

S=π⋅d24S = \frac{\pi \cdot d^2}{4}

where π≈3.14159265\pi \approx 3.14159265.

2. Temperature effect on resistance

The electrical resistivity of metals increases as they heat up. If temperature correction is enabled, resistivity ρ\rho in Ω·mm²/m at temperature TT in °C is:

ρ=ρ20⋅(1+α⋅(T−20))\rho = \rho_{20} \cdot (1 + \alpha \cdot (T - 20))

where:

  • ρ20\rho_{20} is the material resistivity at 20 °C: 0.0175 Ω·mm²/m for copper and 0.0283 Ω·mm²/m for aluminum;
  • α\alpha is the temperature coefficient of resistance: 0.00393 1/°C for copper and 0.00403 1/°C for aluminum;
  • TT is the conductor operating temperature in °C.

If temperature correction is disabled, resistivity at 20 °C is used: ρ=ρ20\rho = \rho_{20}.

3. Electrical resistance and conductance

  • Resistance of one conductor of length LL in meters:

    Rone=ρ⋅LSR_{one} = \rho \cdot \frac{L}{S}
  • Resistance per meter of line:

    Rper_m=ρSR_{per\_m} = \frac{\rho}{S}
  • Out-and-back loop resistance for two conductors in a single-phase line, phase and neutral:

    Rloop=2⋅RoneR_{loop} = 2 \cdot R_{one}
  • Conductance of one conductor, the reciprocal of resistance:

    Gone=1RoneG_{one} = \frac{1}{R_{one}}

4. Voltage drop and power losses

When voltage-drop calculation is enabled, the calculator uses the specified load current II in A and supply voltage UU in V to find:

  • Voltage drop along the line:

    ΔU=I⋅Rloop\Delta U = I \cdot R_{loop}
  • Relative voltage drop as a percentage of nominal supply voltage:

    ΔU%=ΔUU⋅100%\Delta U_{\%} = \frac{\Delta U}{U} \cdot 100\%
  • Active power loss dissipated as heat in the line conductors:

    Ploss=I2⋅RloopP_{loss} = I^2 \cdot R_{loop}

02 / Frequently asked questions

Why account for wire temperature when calculating resistance?

As a metal heats up, thermal vibrations in its crystal lattice make it harder for free electrons to move. Resistance therefore rises, increasing energy losses and voltage drop along the line. Accounting for operating temperature improves the estimate for an electrical network.

Why calculate loop resistance instead of just one conductor?

Current flows from the source to the load through the phase conductor and returns through the neutral in a single-phase circuit. It therefore travels the full cable length twice. Voltage drop and heat losses are based on the out-and-back loop resistance: Rloop=2⋅RoneR_{loop} = 2 \cdot R_{one}.

Electrical resistance is inversely proportional to conductor area: doubling the cross-section halves the resistance. A larger cross-section reduces voltage drop at the end of the line and lowers conductor heating.

Can I use this calculation to choose a cable size?

The calculator estimates the conductor’s physical and electrical properties. Cable sizing for installation must also account for installation conditions, permissible continuous current, short-circuit current, and applicable electrical rules or standards.